ZN63A (VS1) Indoor 12kV Vacuum Circuit Breaker
**Product Overview**
The ZN63A (VS1) indoor high-voltage vacuum circuit breaker is engineered for
three-phase AC systems operating at 50Hz, with a rated voltage range of 7.2–12kV.
Designed for use in indoor switchgear, this unit plays a critical role in the
protection and control of power grid infrastructure and electrical systems within
industrial and mining facilities.
Built to meet rigorous safety and performance standards, the ZN63A (VS1) fully
complies with GB1984-89 for AC high-voltage circuit breakers, JB3855-96 for
3.6–40.5kV indoor vacuum breakers, DL403-91 for 10–35kV technical conditions,
as well as corresponding IEC international standards.
Equipped with a dependable mechanical and electrical interlocking system,
this circuit breaker ensures secure operation and effective fault isolation,
making it a trusted solution for modern power systems that demand
efficiency, safety, and long service life.
Main technical parameters
| Item | Unit | Data |
| rated voltage | kV | 12/24/40.5 |
| Rated frequency | Hz | 50 |
| Rated 1-minute power frequency withstand voltage (phase to phase, ground to ground, port) | kV | 42/65/95 |
| Rated lightning impulse withstand voltage (phase to phase, ground to ground, port) | kV | 75/118/125 |
| Rated operating sequence | O-0.3S-CO-180S-CO |
| Item | Unit | Circuit breaker model | |||||||||
| C-GIS | |||||||||||
| Rated current | A | 630 | 1250 | 1250 | 1600 | 2000 | 2500 | 1250 | 1600 | 2000 | 2500 |
| Rated short circuit breaking current | kA | 20/25 | 31.5 | 40 | |||||||
| Rated short-circuit closing current (peak) | kA | 50/63 | 80 | 100 | |||||||
| Rated continuous short-circuit time | s | 4 | 4 | 4 | |||||||
| Rated short-circuit current breaking times | times | 30 | 30 | 30 | |||||||
| mechanical life | times | 10000 | 10000 | 10000 | |||||||
Mechanical characteristic parameters of circuit breaker
| name | Unit | Data | ||
| Contact opening distance | mm | 12kV/9±1;24kV/13±1;40.5kV/18±1 | ||
| Overtravel | 3.5±0.5 | |||
| Three phase opening and closing at different stages | ms | ≤2 | ||
| Bouncing time of closing contact | ms | 12kV/ ≤ 2; 24kV/ ≤ 2; 40.5kV/≤3 | ||
| Contact pressure of closing contact | N | 20kA | 25kA | 31.5kA |
| 2000±200 | 2400±200 | 3100±200 | ||
| Average opening speed | m/s | 12kV/0.9~1.3; 24kV/1.1~1.6;40.5kV/1.8±0.2 | ||
| Average closing speed | 12kV/0.4~0.8; 24kV/0.6~1.0;40.5kV/0.8±0.2 | |||